Product Details:
Payment & Shipping Terms:
|
Input: | PT100, PT1000, CU50, CU100 | Output: | RS485 |
---|---|---|---|
Mounting Way: | Din-rail Mounting | Power Supply: | 24V DC |
High Light: | converter ad da,universal audio ad converter |
1. General Introduction
The LS-TD4015 is an industrial grade standard RTD acquisition product that supports PT100, PT1000, Cu50, Cu100, Ge53, BA1, BA2, R5000 and R500 6-channel three-wire RTD inputs. RS485 interface is optoelectronic isolated. AD acquisition part is also modulus optoelectronic isolated. It adopts standard MODBUS RTU protocol. Complaint with industry standards, LS-TD4015 is suitable to use for a variety of industrial applications and automation systems. It is convenient to communicate with the host computer and realize a rapid networking and build your monitoring system.
Thermal resistance supports:
PT100 | -200~850℃ | BA1 | -200~650℃ |
PT1000 | -200~850℃s | BA2 | -200~650℃ |
CU50 | -50~150℃ | R5000 | 0~5000Ω |
CU100 | -50~150℃ | R500 | 0~500Ω |
Ge53 | -50~150℃ |
2. Parameter
Technique parameter | Description |
Power supply | 9~30V DC |
Input ranges | PT100,PT1000,Cu50,Cu100,Ge53,BA1,BA2,R5000 and R500 |
Excitation current | 250uA |
Advantage | Each channel supports independent configuration (6 channels can be set separately) |
Input type | 6 channels 3-wire input |
Collect frequency | AD collecting frequency≤10Hz(total rate) |
Resolution | 16 bit |
Accuracy class | ≤ ±0.1%(wiring cable errors not included) |
Input impedance | 20MΩ |
Interface | RS-485 |
Protocol |
Default Modbus-RTU,support 8N1, 8O1, 8E1. Data format: SCADA software, PLC, compatible with ADAM-4015+. If you need MODBUS-ASCII or other, please specify when placing order |
Baud rate | 1200bps, 2400bps, 4800bps, 9600bps, 19200bps, 38400bps, 57600bps, 115200bps |
Distance | RS485 distance<1000m, can use repeater |
Stability | Use high quality chips inside, built-in dual watchdog, reliable and stable operation |
Protection level | Power Pin polarity protection, input Pin photoelectric isolation, AD input Pin and communication port ±15KV ESD protection, isolation voltage 2500Vrms, 500DC continuous, lightning protection, surge protection |
Power consumption | <2000mW |
Weight | 0.3kg |
Mounting way | Standard 35mm U-shaped Din rail installation |
3. Pin Definition
Pin No. | Pin name | Description |
1 | COM4 | Ch 4 COM port |
2 | RTD4- | RTD input ch4- |
3 | RTD4+ | RTD input ch4+ |
4 | COM5 | Ch 5 COM port |
5 | RTD5- | RTD input ch5- |
6 | RTD5+ | RTD input ch5+ |
7 | NC | NC |
8 | NC | NC |
9 | NC | NC |
10 | DATA+ | RS-485 A |
11 | DATA- | RS-485 B |
12 | +VS | Power supply +(9~30V) |
13 | GND | Power supply -(ground of power) |
14 | RTD0+ | RTD input ch0 + |
15 | RTD0- | RTD input ch0 - |
16 | COM0 | Ch0 Com port |
17 | RTD1+ | RTD input ch1+ |
18 | RTD1- | RTD input ch1- |
19 | COM1 | Ch1 Com port |
20 | RTD2+ | RTD input ch2+ |
21 | RTD2- | RTD input ch2- |
22 | COM2 | Ch2 Com port |
23 | RTD3+ | RTD input ch3+ |
24 | RTD3- | RTD input ch3- |
25 | COM3 | Ch3 Com port |
26 | GND | GND |
Contact Person: Sunny
Tel: +8613826574847
433MHz RF Data Module 100mW Wireless Data Transfer 1km RS232 RS485 TTL
433MHz RF Data Module , Wireless Rf Transmitter 2KM Wireless Transceiver Module For AMR
100mW Wireless Data Module 433MHz Wireless Data Transfer For 500m Serial Data
100mW Wireless Data Module RS232 Interface 500m Wireless Data Transmission 433MHz
Intelligent Wireless Irrigation Controller , Irrigation Program Wireless Sprinkler Controller
9-12V Wireless Irrigation Controller Wire Solution Sub Decode Board 128 Station Decode Board
Underground Internet Controlled Sprinkler System Intelligent For Pulse Drive Solenoid
433MHz Wireless irrigation System Solenoid Valve On-Off Control
433MHz Wireless Tank Level Monitoring System HMI wireless control pump ON OFF 2km
2DI2DO PLC Wireless Pump Control / Relay / Valve 433MHz Wireless ON OFF Control
Pump ON-OFF Control System According the Float Switch High Or Low Level
10DI 10DO Wireless Modbus RTU 10 Digital Inputs 10 Relay Outputs 2km Wireless ON OFF Control